TM 5-6115-332-14
P-8-614-14
TO 35C2-3-424-1
Table 4-1. Output Selector Switch Positions and Load Cable Connections (1).
Switch
Cable
Position
Generator Output
Connections
1
240 V, 1 phase, 2 wire
L2 and L3
2
120 V, 1 phase, 2 wire
L2 and L3
3(2)
120 V, 3 phase, 3 wire
L1, L2, and L3
4(2)
120/208 V, 3 phase, 4 wire
LO, L1, L2 and L3
(1) Switch positions are found by facing the
switch. For No. 1 position, turn the knob clockwise
to the limit of its travel. Switch positions 2,3, and 4
may then be found by turning the knob
counterclockwise.
(2) When connecting for a 3-phase, 3-wire, or
3-phase, 4-wire operation, the phase sequence may
be incorrect on some equipment causing motors to
run backward. If the sequence is found to be incor-
rect, switch positions of any two of the load leads ei-
ther L1, L2, and L3. Do not switch load lead LO.
4-3