4-30. Terminal Load Block Assembly
WARNING
Clean all parts in a well-ventilated area.
Avoid inhalation of solvent fumes and
prolonged exposure
of skin to cleaning
solvent.
Wash exposed skin thoroughly.
Dry cleaning solvent (Fed. Spec. P-D-680)
Used to clean parts is potentially danger-
ous to personnel and property. Do not
use near open flame or excessive heat.
Flash point of solvent is 100° to 138° F.
(38° to 59° C.).
(1) Lift cover, tag and disconnect leads.
(2) Remove nuts securing the terminal loads
in the terminal load block assembly.
(3) Remove terminal loads.
(4) Remove screws securing the terminal
load block assembly to the control box and remove
terminal load block.
b. Cleaning.
Clean the terminal load block as-
sembly using a clean cloth dampened in cleaning
solvent, Fed. Spec. P-D-680, and dry thoroughly.
d. Installation.
(1) Secure terminal load block to the control
box with screws.
(2) Install terminal loads and secure with
nuts.
(3) Reconnect leads.
(4) Close cover.
4-31. Ground Strap
c. Inspection and Repair. Inspect terminal load
block assembly for cracks or breaks. Inspect
mounting hardware for thread damage. Replace
damaged terminal load block assembly.
WARNING
Clean all parts in a well-ventilated area.
Avoid inhalation of solvent fumes and
prolonged exposure of skin to cleaning
solvent. Wash exposed skin thoroughly.
Dry cleaning solvent (Fed. Spec. P-D-680)
used to clean parts is potentially danger-
ous to personnel and property. Do not
use near open flame or excessive heat.
Flash point of solvent is 100° to 138° F.
(38° to 59° C.).
a. Removal. Refer to figure 4-29 and the
following instructions and remove the control
panel ground strap.
(1) Remove nuts and lockwashers secur-
ing the control panel ground strap to the
control box and the generator housing.
(2) Remove ground strap.