Table 2-2. Voltmeter Indications
NOTE
The voltages listed in the VOLTMETER INDICATION column are intended to
be read only from the generator set voltmeter. Any voltage reading below the 50
volt mark (in the suppressed portion of the meter) is listed in Table 2-2 as Zero.
Using any voltage indication except Zero below the 50 volt mark will result in
false readings.
OUTPUT
VOLTAGE
VOLTMETER
SELECTOR SWITCH
SELECTOR SWITCH
INDICATION
240 Volt 1 Phase
V0-1
Zero
2 Wire L2 L3
V0-2
60-70
V0-3
60-70
V1-3
60-70
V1-2
60-70
V2-3
240
120 Volt 1 Phase
V0-1
Zero
2 Wire L2 L3
V0-2
Zero
VO-3
Zero
V1-3
Zero
V1-2
Zero
V2-3
117
V0-1
60-70
V0-2
60-70
V0-3
60-70
V1-3
117
V1-2
117
V2-3
117
V0-1
117
V0-2
117
V0-3
117
V1-3
208
V1-2
208
V2-3
208
120 Volt 3 Phase
3 Wire L1 L2 L3
102/208 Volt 3 Phase
4 Wire L0 L1 L2 L3
TM 5-6115-332-14
P-8-614-14
TO 35C2-3-424.1
Change 5
2-10.1/(2-10.2 blank)