TM 5-6115-332-14
P-8-614-14
TO 35C2-3-424-1
(4) Remote Mode Starting. The remote con-
trol terminal board (fig. 2-9) is located on the right
rear of the control box. It provides the connection
points required for starting and stopping the gener-
ator set from a remote position.
TS 6115-332-14/2-9
Figure 2-9. Remote control terminals.
(a) Position the REMOTE-LOCAL switch
(fig. 2-7) in the REMOTE position.
ent temperature is -25°F (-31.7°C) and below it will
(b) To start the generator set from a re-
be necessary to preheat the engine using a blow-
mote positon, make contact between the start ter-
torch (see para. 2-4). After preheating the engine,
minal and the common terminal of the remote con-
proceed with electrical or manual starting as out-
trol terminal board (fig. 2-9). As soon as the unit
lined in (2) and (3), above.
starts, break contact.
c. Stopping.
(1) Local Mode Stopping. Refer to figure 2-
10 for local mode stopping instructions.
2-15
(5) Cold Weather Starting. When the ambi-