TM 5-6115-275-14
NAVFAC P-8-615-14
TO 35C2-3-452-1
(f) Install one end of auxiliary fuel hose to the
fitting on adapter assembly and the other end to the
fitting on the fuel selector valve.
(9) External Power Source. When an auxiliary
power source is needed to start the engine plug battery
cable (with slave plug attached) into slave receptacle (fig.
4-7). Attach opposite end of battery cable to auxiliary
battery or other adequate 24/28 volt direct current
source.
c.
Procedures for Constructing Revetment.
(1) General. This equipment is designed to
operate in the open with unrestricted ventilation. In
some situations it may be necessary to operate the
equipment from the protection of a revetment. This
paragraph provides information of the construction of a
revetment to protect the equipment should it become
necessary.
(2) Dimensions. The minimum allowable in-
side dimensions are shown in figures 4-8, 4-9, and 4-10.
These mimimum dimensions are based soley on
considerations of engine cooling and ventilation, al-
lowing a mimimum practicable amount of space for
maintenance.
TS 6115-275-14/4-7
Figure 4-7. Slave receptacle.
4-8