(f) Saturate the area around the grounding
(c) Bury a inch thick iron or steel plate,
approximately 18 inch x 18 inch size, with ground
(2) Ground cables should be copper. Braided
cable attached, to a depth of at least 4 feet.
cable is the best, but No. 6 AWG gauge (or larger)
(d) Bury a 1/16 inch thick aluminum or
copper wire will suffice.
copper plate approximately 18 inch x 18 inch size,
(3) Connect the ground cable from the ground-
with ground cable attached, to a depth of at least
4 feet.
ing device to the generator set frame ground stud
(e) Position a inch thick iron or steel
plate, or 1/16 inch thick aluminum or copper
c. Connecting Load Cables.
plates, approximately 18 inch x 18 inch size, on
the hard ground or bedrock beneath the trailer
connect the load cables to the AC generator load
stand or roll the wheel of a trailer or truck until it
terminals.
comes to rest on top of the grounding plate.