TM 5-6115-275-14
NAVFAC P-8-615-14
TO 35C2-3-452-1
Table 3-2. Operator/Crew Preventive Maintenance Checks and Services
B-Before Operation
A-After Operation
C-During Operation
Item
Interval
Item to be
Procedures
Equipment is not
No.
Inspected
Check for and have
Ready/Available If:
repaired or adjusted
B
D
A
as necessary
1
Generator Set
a.
Visually inspect the generator set
Class III oil or Class I
for fuel and oil leaks.
fuel
leak is detected.
b.
Check for proper ground connec-
Generator is not
tion.
properly grounded.
c.
Inspect for loose, damaged, or
Any loose, damaged, or
missing parts and unusual wear or
missing parts;
deterioration
(i.e.,spark plugs,
manifolds, starter, or
other items).
d.
Insure load terminal wires are
Loose load terminal
tightened
wires.
e.
Check battery terminals for tightness.
Unservicable or loose
battery terminals.
f.
Visually inspect all controls for ser-
Loose wire connections
viceability before starting generator.
or broken controls.
NOTE
Start generator after visual PMCS;
insure generator operates as stated
in paragraph 2-1.
2
Oil Gage Rod
Check oil level. Add oil as necessary.
3
Controls and
Check for proper operation.
Instruments
a. Current indicator
Indicates percent of applied load, not
meter
to exceed 100%. Rotate ammeter
phase selector switch to monitor load
applied to each phase.
b. Battery charging
Indicates on + side of scale during
Ammeter indicates a
ammeter
normal operation
discharge.
c. Oil pressure gage Normal reading is 20 to 60 psi (1.406
Oil pressure below 20
to 4.218 Kg/sq cm).
psi.
d. AC Voltmeter
Indicates output voltage. Adjust for
Voltage cannot be
desired voltage. Change voltage selec-
adjusted.
tor switch to monitor the voltage for
each phase combination.
e. Frequency meter
Indicates generator frequency.
Meter does not indicate
Normal Readings:
the proper frequency.
MEP-0 1 8A, 60 HZ (red line)
MEP-023A, 400 HZ (red line)
f. Inside instrument
Check for loose wiring, corroded wir-
Faulty wiring or
panel
ing and loose electrical components.
improper mounting of
electrical components.
Change 8 3-3