TM 5-6115-275-14
NAVFAC P-8-615-14
TO 35C2-3-452-1
Figure 4-63. Panel light bulbs, removal and installation.
4-33.
Panel Light Bulbs
a.
Removal. Refer to figure 4-63 and remove the
panel lamps.
b.
Cleaning, Inspection and Repair.
(1)
Clean the lamps with a clean, dry
cloth.
(2)
Inspect the lamps for defects; replace
a defective lamp.
c.
Installation. Refer to figure 4-63 and install the
panel lamps.
4-34.
Panel Lights
a.
Removal.
(1)
Remove lamps, paragraph 4-35.
(2)
Refer to figures 4-61 or 4-62 and
remove the panel lights from the
applicable model generator set.
b.
Cleaning, Inspection and Repair.
(1)
Clean the panel lights with a clean,
dry cloth.
(2)
Inspect
for
broken
or
corroded
terminals, or other defects. Replace
a defective light.
c.
Installation. Refer to figures 4-61 or 4-62 and
install
the
panel
lights
in
the
applicable model generator set.
4-35.
Switches
a.
Removal. Refer to figures 4-61 or 4-62 and
remove
the
switches
from
the
applicable model generator set.
b.
Cleaning, Inspection and Repair.
(1)
Clean the switch with a clean, dry
cloth.
(2)
Inspect for corroded or damaged
terminals, or other defects. Replace
a defective switch.
c.
Instillation. Refer to figures 4-61 or 4-62 and
install the switches in the applicable
model generator set.
4-36.
Time Totalizing Meter
a.
Removal. Refer to figures 4-61 or 4-62 and
remove the time totalizing meter from
the applicable model generator set.
b.
Cleaning, Inspection and Repair.
(1)
Clean meter with a dry, clean cloth.
(2)
Inspect the meter for cracks, breaks
or other damage.
Replace
a
damaged or defective meter.
c.
Installation. Refer to figures 4-61 or 4-62 and
install the time totalizing meter on the
applicable model generator set.
4-37.
Voltage
and
Current
Selectors
and
Voltage
Adjusting Knob, Rheostat
a.
Removal. Refer to figures 4-59, 4-61 or 4-62 and
remove items from applicable model
generator set.
b.
Cleaning, Inspection and Repair.
(1)
Clean the items with a clean, dry
cloth.
(2)
Inspect for damage and improper
operation. Replace if damaged or
defective.
c.
Testing.
(1)
With the electrical leads disconnected
from
the
rheostat,
connect
a
multimeter to both outside terminals.
The resistance measured should not
be more than 10% above or below 15
ohms for generators equipped with
old style voltage regulator, 750 ohms
for
new
universal
style
voltage
regulator.
(2)
Connect the multimeter between the
center terminal and one outside
terminal. Rotate the rheostat from
one extreme position to the other.
The resistance should vary smoothly
from zero to maximum.
d.
Installation. Refer to figures 4-59, 4-61 or 462 and
install items on the applicable model
generator set.
Change 8 4-73