TM 5-6115-275-14
NAVFAC P-8-615-14
TO 35C2-3-452-1
4-38.
Ammeter, Voltmeter: Frequency Meter
a.
Removal. Refer to figures 4-61 or 4-62 and
remove the meters from the
applicable model generator set.
NOTE
el MEP-018A, do not remove wiring on the resistor
board during removal and installation
of the ammeter Remove the two nuts
securing the resistance board to the
ammeter.
b.
Cleaning, Inspection and Repair.
(1)
Clean the meters with a clean, dry
cloth.
(2)
Inspect the meters for broken
glass, improper operation, or
other
damage.
Replace
if
damaged or defective.
c.
Testing of AC Voltmeter, Ammeter and
Frequency meter. Test meters
using a multimeter. Refer to
paragraph 4-15.
d.
Installation. Refer to figures 4-61 or 4-62 and
install
the
meters
on
the
applicable model generator set.
NOTE
el MEP-018A, secure resistor board to ammeter
with two nuts.
4-39.
Cabinet Cable Harness
a.
General. Wiring harnesses are utilized for the
interconnection
of
the
components of the generator set.
Terminals and leads of the wiring
harness may be removed from
the terminals for the replacement
of components. Individual wires,
not part of the wiring harness,
may be replaced.
b.
Tagging. When replacing controls and
instruments, tag the electrical
leads
that
have
been
disconnected
to
facilitate
reinstallation.
c.
Repair. If there is a break in the insulation of
a
wire,
repair
the
broken
insulation by wrapping the bare
area with electrical tape. If there
is a break in a wire that is
accessible, repair by cutting back
the insulation, twisting the ends
together, solder the connection
and wrap with electrical tape. If a
terminal is damaged or lost,
replace it by using a wire terminal
repair kit. Remove a wire that
cannot be repaired and replace it
with a new wire of the same size
and gage. Identify the new wire
with the same identification as the
one removed.
4-40.
Fuses
a.
Removal. Refer to figure 4-64 and remove
the fuses and fuseholders.
Figure 4-64. Fuses, removal and installation.
b.
Cleaning, Inspection and Repair.
(1)
clean the fuses and fuseholder
with a clean, dry cloth.
(2)
Inspect the fuses for visible
damage, replace a defective fuse.
c.
Installation. Refer to figure 4-64 and install
the fuse and fuseholders.
4-41.
Doors and Outlet Receptacle
a.
Removal. Refer to figure 4-65 and 4-66 and
remove items from the applicable
model generator set.
4-74