TM 5-6115-596-14
GENERATOR-REGULATOR MAINTENANCE PROCEDURES
Section VIII.
General .
5-27.
This section contains instructions for removal,
a.
Scope .
disassembly, inspection and repair, assembly and installation of
the generator regulator in generator sets, serial numbers 923-001
For generator sets, serial numbers 929-001 thru
thru 923-553.
929-290, the regulator is non-repairable so only the paragraphs
on removal and installation are applicable, as will be noted
Also, this section covers the removal, inspection and
below.
installation of the generator regulator resilient mounts.
b.
Description .
serial numbers 923-001 thru 923-553) consists of a relay assembly
The
and voltage regulator assembly bound in a watertight case.
generator regulator in generator sets, serial numbers 929-001
both
thru 929-290 is a single assembly in a sealed case.
For
regulators, connection is made to integral parts of the case
through a pin-type connector and a socket-type connection mounted
on top of the case.
Removal.
5-28.
a.
Make certain all power is turned OFF.
b.
Disconnect wiring harness (1) at regulator battery connector
(2) and regulator generator connector (12).
c.
Remove screw (3), and disconnect ground leads (4) at top of
regulator (9).
d.
Remove four screws (5) and eight washers (8) securing regula-
tor ground lead (6) and regulator to mounts (13) on inner frame (14).
e.
Disconnect ground lead (6), and remove regulator from mounts.
5-44 Change 2