TM 5-6115-275-14
NAVFAC P-8-615-14
TO 35C2-3-452-1
constant loads from no-load to
rated-load during any 30 to 45
second period of operation.
Rated load is rated kw at 0.8
power factor.
Long-term,
steady-state
stability
The long-term steady- state
frequency does not exceed +1%
of rated frequency at constant
loads from no-load to rated load
during any 4 hour period of
continuous operation. Long-
term, steady-state frequency
deviation is defined as the
amount the frequency deviates
from the reference (mean of the
observed
band)
frequency
determined at the beginning of
the long-term stability test.
Transient
response
Following any sudden increase
in load, including from no-load to
rated-load,
the
governing
system will reestablish stable
engine
operating
conditions
(stable
engine
operating
conditions are the conditions
specified
from
steady-state
performance) within 4 seconds,
and the maximum transient
frequency change below the
new steady-state frequency is
not more than 3% of the rated
frequency.
Following
any
sudden de-
crease in load, including from
rated-load to no-load, the
governing
system
will
reestablish
stable
engine
operating conditions within 6
seconds, and the maximum
transient
frequency
change
above the new steady-state
frequency is not more than 5%
of rated frequency.
t.
Voltage Regulation Specifications
(Model MEP-023A).
Voltage
regulation
The voltage regulation from no-
load to rated load and from
rated-load to no-load does not
exceed 4% of the rated voltage
for all connections except for the
single-phase, two wire, 240 volt
connection. For this connection,
the regulation will not exceed
5% of the rated voltage.
Steady-state
performance
At constant loads from no-load
to rated load, the voltage at the
set terminals will not deviate
more than 1% from its average
rms. (root mean square) value.
Transient
response
Following
sudden
load
changes from rated load to no-
load, the instantaneous rms.
voltage will remain within a
bandwidth of + 30% of the no-
load voltage as measured by a
magnetic oscillograph having a
no-load voltage deflection of not
less than 31/2 inches(8.89 cm).
Stable operation will reestablish
within 2 seconds at normal
ambient conditions, and within
4 seconds at 250 and +125°F.
(40 and 52°C).
1-19