TM 5-6115-275-14NAVFAC P-8-615-14TO 35C2-3-452-1r.Generator Repair and OverhaulData (Model MEP0I18A).(1). Stator.Number of slots36Number of coils72Coil span12/12/12,120"phase beltsCoil pitch1 to 16Wire sizeNo. 16 AWG (AmericanWire Gage)Type of wireCopperDippingcompoundsType M, grade CB varnishper MIL-IL24092Resistance0.127 ohms +10%(2)Rotor.Number of poles2Number of coils2Turns per coil475Wire sizeNo16 AWGType of wireCopperDippingcompoundsType M, grade CB varnishper MIL-I-24092Ring toring resistance6.8 ohms +10%(3)Exciter Armature.Number of coils90Number of poles4Number of dots45Number of coilsper slot2Turn per coil4Wire sizeNo.20 AWGType of wireCopperDippingcompoundType M, grade CB varnishper MIL-I-24092.Resistance.42 ohms +10%(4)Exciter FieldNumber of coils6Turns per coil190Wire sizeNo. 20 AWGType of wireCopperNumber of poles6Resistance8 ohms +10%DippingcompoundsType M, grade CB varnishper MIL-I-24092(5)Frequency Performance.FrequencyregulationThe frequency regulation shall notexceed three percent with thefrequency adjustment constantFrequency regulation is the rated-load frequency divided into thedifference between the no-loadfrequency and the rated-loadfrequency.Short-term,steady-statestabilityThe governing system shallautomatically maintain the short-term, steady-state frequency ofthe set within a band width ofplus or minus ½ of one percentof the rated frequency at constantload from no load to rated loadduring any 30 second period ofoperation. Rated load is ratedKW at 0.8 power factor.Long-term,steady-statestability The long-term, steady-state frequencydeviation shall not exceed plus orminus one percent of the ratedfrequency at constant loads fromno load to rated load during any 4hour period of continuousoperation except that twofrequency excursions beyond thespecific. band width for any 4hour period are permitted. Longterm, steady- state frequencydeviation is defined as theamount the frequency1-17
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business