Use a multimeter set on the RXI ohm scale and test
between terminals I and 2, 3 and
4, and 5 and 6. If continuity is not
indicated in all three cases, the
transformer is defective and must
be replaced. Before reinstalling
the
resistors
test
each
to
determine if they have a reading
within 1% of 150 ohms. Replace
any defective resistor.
e.
Installation. Refer to figure 7-1 or 7-2 and
install the current transformer on
the applicable model generator
set.
7-12.
Output Terminal Board
a.
Removal. Refer to figure 7-1 or 7-2 and
remove the output terminal board
from
the
applicable
model
generator set.
b.
Cleaning, Inspection, and Repair.
WARNING
Clean all parts in a well-ventilated area. Avoid inhalation of
solvent fumes and prolonged exposure
of skin to cleaning solvent. Wash
exposed skin thoroughly. Dry cleaning
solvent (Fed. Spec. P-D680 and P-S-
661) used to clean parts is potentially
dangerous to personnel and property.
Do not use near open flame or
excessive heat. Flash point of solvent is
1OOF (38C).
(1)
Clean items with cleaning solvent,
Fed. Spec. P-D-680 or P-S-66
1, and dry thoroughly.
(2)
Inspect for damage and defects
and replace defective terminals or
terminal board as necessary.
c.
Installation. Refer to figure 7-1 or 7-2 and
install the output terminal board
on the applicable model generator
set.
7-14.8 Change 8