TM 5-6115-271-14
TO 35C2-3-386-1
TM 05926A-14
NAVFAC P-8-613-14
Table 3-2. OPERATOR/CREW PREVENTIVE MAINTENANCE CHECKS AND SERVICES
A-AFTER OPERATION
B-BEFORE OPERATION
D-DURING OPERATION
INTERVAL
EQUIPMENT IS
PROCEDURES
ITEM TO BE
NOT READY
CHECK FOR AND HAVE REPAIRED
D
A
ITEM
B
NO.
INSPECTED
AVAILABLE IF:
OR ADJUSTED AS NECESSARY
Generator is not
Generator set
1
q
gounded properly.
tight ground connections and
proper ground rod installation.
Class III oil
Gages and
2
leakage or any fuel
operation.
Instruments
leaks are detected.
Models MEP-016A
and
MEP-021A
Voltage cannot be
Adjust for desired voltage.
q
adjusted.
Rotate voltage selector switch
to monitor the various output
Indicates
Normal indication:
q
MEP-021A; 400 Hz (392 to
meter
or too low.
408)
MEP-016A, 60 Hz (59 to
61)
Indicates percentage of applied
c. Load meter
q
load. Rotate current selector
switch to monitor the load
applied to each phase. Not to
exceed 100%.
Model MEP-026A
Voltage cannot be
Adjust for proper DC volts
q
adjusted.
(must not exceed 28 V max).
Change 10