b. Cleaning, Inspection and Repair.
(1) Carefully and thoroughly clean the exte-
rior of the voltmeter with a clean lint free cloth.
(2) Inspect the voltmeter for signs of burned
areas, damaged threads, loosened contacts, and for
loose or broken glass.
(3) Replace a damaged or defective voltmeter.
c. Installation.
(1) Secure voltmeter to the control panel with
screws, washers, and nuts.
(2) Reconnect wiring.
d. Testing. Test voltmeter by connecting an ad-
ditional voltmeter to load terminals of generator set
and taking comparative reading to establish valid-
ity of generator set voltmeter.
4-34. Frequency Meter (M1).
a. Removal. Refer to figure 4-24 and the follow-
ing instructions to remove the frequency meter.
(1) Tag and disconnect leads from the fre-
quency meter.
(2) Remove nuts, washers, and screws secu-
ring the frequency meter to the control panel.
(3) Remove frequency meter.
b. Cleaning, Inspection and Repair.
(1) Carefully and thoroughly clean the exte-
rior surfaces of the frequency meter with a clean
lint free cloth.
(2) Inspect the frequency meter for signs of
burned areas, damaged threads, loosened contacts,
and for loose or broken glass.
(3) Replace a damaged or defective frequency
meter.
c. Installation.
(1) Position frequency meter in place on con-
trol panel and secure with screws, washers, and
nuts.
(2) Reconnect leads.
d. Testing.
(1) Disconnect frequency meter leads and con-
nect a frequency meter of known quality and take
comparative readings to establish validity of gener-
ator set frequency meter.
(2) Reconnect leads.
4-35. Current Indicator Meter (M5).
a. Removal. Refer to figure 4-24 and the follow-
ing instructions to remove the current indicator me-
ter.
(1) Tag and disconnect leads.
(2) Remove nuts, washers, and screws secu-
ring the current indicator meter to the control pan-
(3) Remove the current indicator meter.
b. Cleaning, Inspection and Repair.
(1) Carefully and thoroughly clean the exte-
rior surfaces of the current indicator meter with a
clean lint free cloth.
(2) Inspect the current indicator meter for
signs of burned areas, damaged threads, loosened
terminals, and for loose & broken glass.
(3) Replace a damaged or defective current in-
dicator meter.
c. Installation.
(1) Position the current indicator meter in
place on the control panel and secure with screws,
washers, and nuts.
(2) Reconnect leads.
d. Testing.
(1) Disconnect current indicator meter and
connect a current indicator meter of known quality
and take comparative readings to establish validity
of generator set current indicator meter.
(2) Reconnect leads.
4-36. Ammeter Phase Selector Switch
(S2).
a. Removal. Refer to figure 4-24 and the follow-
ing instructions to remove the ammeter phase selec-
tor switch.
(1) Tag and disconnect leads from the am-
meter phase selector switch.
(2) Loosen setscrew securing control knob on
the ammeter phase selector switch and remove
knob.
(3) Remove locking nut and washer securing
the ammeter phase selector switch to the control
panel.
(4) Remove the ammeter phase selector
switch.
b. Cleaning, Inspection and Repair.
(1) Carefully and thoroughly clean the exte-
rior surfaces of the ammeter phase selector switch
using a clean lint free cloth.
(2) Inspect switch for signs of burned areas,
damaged threads, cracks, or loosened contacts.
(3) Replace a damaged or defective ammeter
phase selector switch.
c. Installation.
(1) Position the ammeter phase selector
switch in place on the control panel and secure with
washer and nut.
(2) Place control knob over end of switch shaft
and secure by tightening setscrew.
(3) Reconnect leads.
el.