TM 5-6115-275-14
NAVFAC P-8-615-14
TO 35C2-3-452-1
Figure 1-4. Generator set, right front, three-quarter
view (Model MEP-A).
c. Generator.
(1)
The Model MEP-023A generator is an
On Model 10 GFG40XR/E5885A,with a direct-
connected, brushless, rotating exciter, 0.8 pf (power
factor) 400 hertz, 3428 rpm (revoltions per minute). The
generator is rated at 10 KW (Kilowatts), with the
following characteristics: 120V, one-phase, two wire;
240 volts, one-phase, two wire: 120 volts, three-phase,
three-wire; 120/208 volts three-
phase, four-wire. The generator is self-cooled by
internal fan.
(2)
The Model MEP-018A generator is 60
hertz. The voltage rating is120/240 and 120, 1 phase
and 120/20 8 and 120, 3 phase to voltage ratings. The
amperage is 3 phase connection load current, 34.7
amperes per line, 1 phase connection load current, 104
amperes and 52 amperes load current on 240 volt
connection.
1-6 Change 4