Test (Model MEP-018A).
(1)
Apply ac input of 120 volts. 60
hertz current across terminals
marked "L".
(2)
With panel meter (M3) connected
to output side meter reading
should indicate 60 hertz to plus or
minus 0.5 hertz.
(3)
For
test
with
panel
meter
disconnected,
direct
output
current of the converter shall be
100 microamperes plus or minus
10 microamperes with 1100 ohm
load across positive and negative
termi-
nals. Replace a defective frequency converter.
f.
Installation. Refer to figure 7-1 or 7-2 and
install the converter on the
applicable model generator set.