TM 5-6115-271-14
TO 35C2-3-386-1
TM-05926A-14
NAVFAC P-8-613-14
Maximum Droop (Maximum Frequency Regulation)
Model
3-KW, 60 Hz
3-KW, 400 Hz
3-KW, 28VDC
MEP-016A
MEP-021A
MEP-026A
RPM
3600
3428
3600
A
--
Frequency
400 Hz
60 Hz
RPM
3708
3530
3708
B
--
Frequency
61.8 Hz
412 Hz
STEP 1. Move the governor control knob to the GOVERN or RUN position.
STEP 2. Start engine and allow engine to warmup at rated speed for 3 to 5 minutes.
STEP 3. Apply load. Loosen locknut A and turn minimum speed stop screw to obtain engine speed/frequen-
cy given in lines A of above table. Tighten locknut A.
STEP 4. Disengage load and check engine speed/frequency. If speed/frequency does not exceed values given
in table above, lines B, no further adjustment is necessary. If speed exceeds values of table above,
lines B, perform steps 5 and 6.
STEP 5. Loosen locknut B and turn governor spring adjustment nut clockwise 4 turns. Tighten locknut B.
STEP 6. Perform steps 3 and 4. NOTE: If no-load speed is adjusted too close to load speed, instability or hunt-
ing will occur. If instability occurs, adjust governor spring adjustment nut to obtain no-load speed/fre-
quency indicated in Table 1, Column B. Then perform steps 3 and 4 to obtain stability.
Figure 2-10.1 Governor Adjustment using Frequency Meter (Sheet 2 of 2).
Change 9
2-14.1